APC MGE Galaxy 5500 UPS

APC MGE Galaxy 5500 UPS


20 – 120 kVA state-of-the-art three-phase power protection designed to meet a wide range of requirements from medium
data centers to industrial and facilities applications.

Product Snapshot
Normal AC supply input
Input voltage (V): 250 V1 to 470 V, three-phase
Normal and bypass AC inputs: separate, common in option
Frequency (Hz): 45 – 66 Hz
Input power factor: > 0.99
THDI < 3% full load
Bypass AC Input
Input voltage range: (380 V, 400 V, 415 V) +/- 10%
Frequency: 50 Hz/60 Hz +/- 10%
Output
Phase to phase output voltage (V): 380 V/400 V/415 V, three-phase + neutral
Output frequency: 50 or 60 Hz +/- 0.1%
Overload capacity utility operation: 125% for 10 minutes; 150% for 60 seconds
Output voltage regulation: +/- 1%
Voltage distortion (THD): < 2% Phase-to-phase and Phase-to-neutral for non-linear loads
Output voltage tolerance: +1% static, +/- 2% at 100% load step
Load power factor: 0.9
Overall efficiency
Efficiency at full load (AC-AC) at 100% load: Up to 94%
ECO mode: up to 97%2
Communication and management
Control panel: Multifunction LCD, status, and control console
Model
 
Height (mm)
Width (mm)
Depth (mm)
Weight (kg)
Auxillary cabinet narrow
1900
712
850
135
Auxillary cabinet wide
1900
1012
850
150
Auxillary cabinet 475 mm with isolation transformer, up to 60kVA
1900
475
850
118 min. 305 max
Auxillary cabinet 550 mm with isolation transformer, 80-120kVA
1900
550
850
118 min. 527 max.
UPS without battery
1900
712
850
400/520
UPS with internal battery
1900
1112
850
UPS with transformer
1900
1190/1265
850
705/1045
Battery cabinet narrow
1900
712
850
135
Battery cabinet wide
1900
1012
850
150
Parallel system bypass (wallmounted or cabinet configuration)
1000 min1900 max.
800 min1010 max.
303 min 850 max.
71 min. 280 max.
  • IGBT-based technology for power quality - Supplies clean, stable power to sensitive loads, ensuring critical power protection, optimum performance, and extended life.
  • Dual input - Allows for connection to two separate input sources for increased availability.
  • Parallel operation - Connect as many as six units in parallel for capacity and redundancy to grow with your power requirements.
  • Redundant components - Provides increased backup for greater reliability and ensures continuous operation.
  • Built-in static and maintenance bypass - Enables the UPS unit to transfer the load to utility power, without interruption, in the event of heavy overload or fault.
  • Pre-installed network management card - Allows for easy network integration, compliant with IP v6, SNMP v3, and PowerChute™ suite.
  • Footprint optimization with "All in one box" configuration -  In some configurations the UPS unit includes batteries on its frame to reduce the footprint.

Please see available files below:

APC MGE Galaxy 5500 Brochure

  • Parallel system bypass cabinets
  • IP32 rated cabinets
  • External maintenance bypass, (wall-mounted or standalone)
  • Top cable entry cabinet
  • Communications cards
  • Advanced power management software
  • Compact transformer
  • Full capable back feed protection option
  • Additional protection with optional IEC filter
  • Synchronization option (to synchronize UPS unit with external source)
Do you have a similar problem? We can help.
Call 1300 191 365 or email support@fusionps.com.au

Think these products may suit an issue you have?
For sales questions and information

Get in touch a member of our helpful sales team:

Call 1300 911 365 (Local call)
For international customers +61 3 8677 5600
Monday – Thursday / 8am – 7pm EST
Friday 8am – 6pm EST
Email
sales@fusionps.com.au

Write a review

security


No Reviews | Be the first person to write a review on this product!