Alpha CXPS standard power systems bring proven Cordex technology into a standard integrated system package. The CXPS 48-1T uses high density 48V-3.6kW rectifiers, the front access single-tier distribution, and the advanced CXCM4 digital controller. The CXPS 48-2T uses high density 48V-3.6kW rectifiers, the front access two-tier distribution, and the advanced CXCM4 digital controller.

Product Snapshot
Input
Voltage: 176 to 320Vac
Current: 16.8A @ 240Vac nominal (per rectifier module)
Frequency: 45 to 66Hz
Power factor: >.99
Output
Voltage: 42 to 60Vdc
 
CXPS 48-1T
CXPS 48-2T
Current:
System: 375A (expandable to 600A with additional CXRF shelf) Rectifier: 75A @ 48Vdc
System: 825A (expandable to 1200A with additional CXRF shelf) Rectifier: 75A @ 48Vdc
Power:
System: 18.0kW (expandable to 28.8kW with additional CXRF shelf) Rectifier: 3600W max
System: 39.6kW (expandable to 57.6kW with additional CXRF shelf) Rectifier: 3600W max
Model
Parts Number
Height (mm)
Width (mm)
Depth (mm)
Weight (kg)
053-392-20
488
584
477
49.8
053-393-20
755
584
477
70.3

CXPS 48-1T (with LVD)

  • Configurations
    • 053-392-20-000 - Base system with 23" mounting.
    • 053-392-20-010 - System mounted in 22RU (½ height) battery mount rack.
    • 053-392-20-020 - System mounted in 44RU Zone 4 seismic rack.
    • 053-392-20-030 - System mounted in 44RU Z4 rack with 3x battery trays for 3x 48V strings.
  • Rectifier - Up to 5x 48V-3.6kW rectifier positions.
  • Distribution
    • 18x AM plug-in breaker positions.
    • 10x GMT type fuse positions.
    • Shunt
    • Low voltage disconnect.
  • Controller - CXCM4 modular controller.

CXPS 48-1T_b (no LVD)

  • Configurations
    • 053-692-20-000 - Base system with 23" mounting.
    • 053-692-20-020 - System mounted in 44RU Zone 4 seismic rack.
    • 053-692-20-030 - System mounted in 44RU Z4 rack with 3x battery trays for 3x 48V strings.
  • Rectifier - .Up to 5x 48V-3.6kW rectifier positions.
  • Distribution
    • 24x AM plug-in breaker positions.
    • 10x GMT type fuse position.
    • Shunt
  • Controlle - CXCM4 modular controller.

CXPS 48-2T (with LVD)

  • Configurations
    • 053-393-20-000 - Base system with 23" mounting.
    • 053-393-20-010 - System mounted in 22RU (½ height) battery mount rack.
    • 053-393-20-020 - System mounted in 44RU Zone 4 seismic rack.
    • 053-393-20-030 - System mounted in 44RU Z4 rack with 3x battery trays for 3x 48V strings.
  • Rectifier - Up to 11x 48V-3.6kW rectifier positions .
  • Distribution
    • 38x AM plug-in breaker positions.
    • 10x GMT type fuse positions.
    • Shunt.
    • Low voltage disconnect.
  • Controller - CXCM4 modular controller.

CXPS 48-2T_b (no LVD)

  • Configurations
    • 053-693-20-000 - Base system with 23" mounting.
    • 053-693-20-020 - System mounted in 44RU Zone 4 seismic rack.
    • 053-693-20-030 - System mounted in 44RU Z4 rack with 3x battery trays for 3x 48V strings.
  • Rectifier - Up to 11x 48V-3.6kW rectifier positions.
  • Distribution
    • 48x AM plug-in breaker positions.
    • 10x GMT type fuse positions.
    • Shunt.
  • Controller - CXCM4 modular controller.

Please see available files below:

Alpha CXPS 48-1T Brochure 

Alpha CXPS 48-2T Brochure

There are no additional options for the Alpha Cordex CXPS 48-XT.
Do you have a similar problem? We can help.
Call 1300 191 365 or email support@fusionps.com.au

Think these products may suit an issue you have?
For sales questions and information

Get in touch a member of our helpful sales team:

Call 1300 911 365 (Local call)
For international customers +61 3 8677 5600
Monday – Thursday / 8am – 7pm EST
Friday 8am – 6pm EST
Email
sales@fusionps.com.au

Write a review

security


No Reviews | Be the first person to write a review on this product!